HPlogo 900 Series HP 3000 Computer Systems: MPE/iX Error Messages Manual Volume II > Chapter 18 UPS

(Uninterrupted Power Source)

» 

Technical documentation

Complete book in PDF
» Feedback

 » Table of Contents

33

MESSAGE

UPS LDEV ! reports loss of AC input power. (UPSERR 0033)

CAUSE

The specified UPS device reported that it detected an input power failure. There has been an AC power failure somewhere in the power path leading into the UPS. The UPS has switched to its internal battery pack to supply reserve power.

ACTION

If the power failure is brief, not long enough to exhaust the UPS battery, no action is needed. Otherwise, determine what is causing the power loss and take action to restore the power before the UPS battery becomes exhausted.

35

MESSAGE

UPS LDEV ! reports AC input power "Bypass Mode". (UPSWRN 0035)

CAUSE

The specified UPS device has been placed into its "AC Power Bypass Mode" of operation. This should only occur when an HP Customer Engineer is servicing the UPS and intends to put the UPS into "Bypass Mode".

ACTION

No action is needed if this message occurs during Customer Engineer servicing of the UPS.If this message occurs during normal system operation, there is probably a hardware problem in the UPS. Call your HP service representative.

36

MESSAGE

UPS LDEV ! reports AC input power restored. (UPSWRN 0036)

CAUSE

The specified UPS device had lost its AC input power in the past, and now the AC input power has been restored. If the UPS is operating correctly, it will now switch from battery operation back to normal AC power operation.

ACTION

No action is needed. The system automatically returns to normal operation when all UPS devices (there may be one or several UPS devices on a system) detect that normal AC input power is present following a power loss at any UPS.

37

MESSAGE

UPS LDEV ! reports "Low Battery Charge" condition. (UPSWRN 0037)

CAUSE

The specified UPS had lost its AC input power some time ago and has been supplying reserve power from its battery. AC input power has not been restored yet, causing the battery to be drained down to a "low charge" power level.

ACTION

Locate and correct the cause of the AC power failure. If AC power is not restored within the next two minutes, the UPS battery will be exhausted and the UPS output AC power will fail, causing power loss to the computer equipment.

41

MESSAGE

UPS LDEV ! reports AC output power turned off. (UPSERR 0041)

CAUSE

The specified UPS device has turned off its AC output power. Someone may have mistakenly turned off the UPS' power switch, or the UPS may have malfunctioned. Whatever equipment was receiving power from the UPS has now lost power.

ACTION

Investigate and correct the problem at the UPS. Turn on all power control switches on the UPS. If the computer (CPU) lost power, you will have to re-boot the system after restoring the UPS power.

128

MESSAGE

UPS LDEV ! reports UPS "System Fail" condition cleared. (UPSWRN 0128)

CAUSE

Some time ago, the specified UPS device had reported a UPS "System Failure" condition. Now, the "System Failure" condition within the UPS device has been corrected and the UPS is reporting that it has returned to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

129

MESSAGE

UPS LDEV ! reports UPS "Inverter Fail" condition cleared. (UPSWRN 0129)

CAUSE

Some time ago, the specified UPS device had reported a UPS "Inverter Failure" condition. Now, the "Inverter Failure" condition within the UPS device has been corrected and the UPS is reporting a return to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

130

MESSAGE

UPS LDEV ! reports UPS "Battery Not Present" condition cleared. (UPSWRN 0130)

CAUSE

Some time ago, the specified UPS device had reported a "Battery Not Present" condition. Now, the "Battery Not Present" condition within the UPS has been corrected and the UPS is reporting that it has returned to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

131

MESSAGE

UPS LDEV ! reports UPS "Charger Fault" condition cleared. (UPSWRN 0131)

CAUSE

Some time ago, the specified UPS device had reported a UPS "Charger Fault" condition. Now, the "Charger Fault" condition within the UPS device has been corrected and the UPS is reporting that it has returned to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

132

MESSAGE

UPS LDEV ! reports UPS "Overload Shutdown" condition cleared. (UPSWRN 0132)

CAUSE

Some time ago, the specified UPS device had reported an "Overload Shutdown" condition. Now, the "Overload Shutdown" condition within the UPS device has been corrected and the UPS is reporting a return to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

133

MESSAGE

UPS LDEV ! reports UPS "High Ambient Temperature Shutdown" condition cleared. (UPSWRN 0133)

CAUSE

Some time ago, the specified UPS device had reported a "UPS High Ambient Temp- erature Shutdown" condition. Now, the "High-Ambient Temperature Shutdown" con- dition has been corrected. The UPS is reporting a return to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

134

MESSAGE

UPS LDEV ! reports UPS "Overload" condition cleared. (UPSWRN 134)

CAUSE

Some time ago, the specified UPS device had reported a UPS "Overload" condition. Now, the UPS "Overload" condition has been corrected and the UPS is reporting that it has returned to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

135

MESSAGE

UPS LDEV ! reports UPS "High Ambient Temperature" condition cleared. (UPSWRN 0135)

CAUSE

Some time ago, the specified UPS device had reported a UPS "High Ambient Temp- erature" condition. Now, the "High Ambient Temperature" condition has been corrected and the UPS is reporting that it has returned to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

136

MESSAGE

UPS LDEV ! reports UPS "Battery Test Fail" condition cleared. (UPSWRN 0136)

CAUSE

Some time ago, the specified UPS device had reported a UPS "Battery Test Fail" condition. Now, the "Battery Test Fail" condition within the UPS device has been corrected and the UPS is reporting a return to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

137

MESSAGE

UPS LDEV ! reports UPS "High Battery Voltage" condition cleared. (UPSWRN 0137)

CAUSE

Some time ago, the specified UPS device had reported a UPS "High Battery Volt- age" condition. Now, the "High Battery Voltage" condition in the UPS device has been corrected and the UPS is reporting a return to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

138

MESSAGE

UPS LDEV ! reports UPS "Low Battery Voltage" condition cleared. (UPSWRN 0138)

CAUSE

Some time ago, the specified UPS device had reported a UPS "Low Battery Volt- age" condition. Now, the "Low Battery Voltage" condition in the UPS device has been corrected and the UPS is reporting a return to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

139

MESSAGE

UPS LDEV ! reports UPS "High Output Voltage Shutdown" condition cleared. (UPSWRN 0139)

CAUSE

Some time ago, the specified UPS device had reported a UPS "High Output Volt- age Shutdown" condition. Now, the "High Output Voltage Shutdown" condition has been cleared and the UPS is reporting a return to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

140

MESSAGE

UPS LDEV ! reports UPS "Low Output Voltage Shutdown" condition cleared. (UPSWRN 0140)

CAUSE

Some time ago, the specified UPS device had reported a UPS "Low Output Voltage Shutdown" condition. Now, the "Low Output Voltage Shutdown" condition has been corrected and the UPS is reporting a return to normal operation.

ACTION

No action is needed. This message merely confirms that a previously reported problem has been corrected.

192

MESSAGE

UPS LDEV ! reports UPS "System Fail" condition. (UPSERR 0192)

CAUSE

The specified UPS device reported a UPS "System Failure" condition. This is a hardware malfunction condition within the UPS.

ACTION

Call your Hewlett-Packard service representative.

193

MESSAGE

UPS LDEV ! reports UPS "Inverter Fail" condition. (UPSERR 0193)

CAUSE

The specified UPS device reported a "UPS Inverter Fail" condition. This is a hardware malfunction condition within the UPS. The DC-to-AC power inverter within the UPS has malfunctioned.

ACTION

Call your Hewlett-Packard service representative.

194

MESSAGE

UPS LDEV ! reports UPS "Battery Not Present" condition. (UPSERR 0194)

CAUSE

The specified UPS device reported a "Battery Not Present" condition. This is a hardware malfunction condition within the UPS. The UPS hardware logic perceives that the UPS battery pack is not connected.

ACTION

Call your Hewlett-Packard service representative.

195

MESSAGE

UPS LDEV ! reports UPS "Charger Fault" condition. (UPSERR 0195)

CAUSE

The specified UPS device reported a UPS "Charger Fault" condition. This is a hardware malfunction condition within the UPS. The UPS' internal battery charger circuitry has malfunctioned.

ACTION

Call your Hewlett-Packard service representative.

196

MESSAGE

UPS LDEV ! reports UPS "Overload Shutdown" condition. (UPSERR 0196) \CAUSE\ The specified UPS device reported a UPS "Overload Shutdown" condition. Too much power was being drawn from the UPS AC output by the computer equipment being powered from this UPS. That equipment may be malfunctioning.

ACTION

Call your Hewlett-Packard service representative.

197

MESSAGE

UPS LDEV ! reports UPS "High Ambient Temperature Shutdown" condition. (UPSERR 0197)

CAUSE

The specified UPS device reported a UPS "High Ambient Temperature Shutdown" condition. The temperature of the UPS hardware became too high to permit safe operation, and the UPS turned itself off to prevent equipment damage.

ACTION

If the computer room has become too warm, take steps to cool the room. If room temperature is not the problem, there has probably been a hardware malfunction. Call your Hewlett-Packard service representative.

198

MESSAGE

UPS LDEV ! reports UPS "Overload" condition. (UPSERR 0198)

CAUSE

The specified UPS device reported a UPS "Overload" condition. The equipment being powered by the UPS is drawing too much power from the UPS AC output. If the excessive power draw continues, the UPS may reach an "Overload Shutdown".

ACTION

Call your Hewlett-Packard service representative.

199

MESSAGE

UPS LDEV ! reports UPS "High Ambient Temperature" condition. (UPSERR 0199)

CAUSE

The specified UPS device reported a UPS "High Ambient Temperature" condition. The UPS has detected an abnormally high temperature in the UPS hardware. If the temperature rises further, the UPS may reach "High Temperature Shutdown".

ACTION

If the computer room has become too warm, take steps to cool the room. If room temperature is not the problem, there has probably been a hardware malfunction. Call your Hewlett-Packard service representative.

200

MESSAGE

UPS LDEV ! reports UPS "Battery Test Fail" condition. (UPSERR 0200)

CAUSE

The specified UPS device reported a UPS "Battery Test Fail" condition. This is a hardware malfunction within the UPS hardware. The UPS logic perceives that the UPS battery is not working properly.

ACTION

Call your Hewlett-Packard service representative.

201

MESSAGE

UPS LDEV ! reports UPS "High Battery Voltage" condition. (UPSERR 0201)

CAUSE

The specified UPS device reported a UPS "High Battery Voltage" condition. This is a hardware malfunction within the UPS hardware. The UPS logic perceives that the UPS battery is not working properly.

ACTION

Call your Hewlett-Packard service representative.

202

MESSAGE

UPS LDEV ! reports UPS "Low Battery Voltage" condition. (UPSERR 0202)

CAUSE

The specified UPS device reported a UPS "Low Battery Voltage" condition. This is a hardware malfunction within the UPS hardware. The UPS logic perceives that the UPS battery is not working properly.

ACTION

Call your Hewlett-Packard service representative.

203

MESSAGE

UPS LDEV ! reports UPS "High Output Voltage Shutdown" condition. (UPSERR 0203)

CAUSE

The specified UPS device reported a UPS "High Output Voltage Shutdown" condi-tion. This is a hardware malfunction within the UPS hardware or possibly in the equipment being powered from the UPS. The UPS has shut itself off.

ACTION

Call your Hewlett-Packard service representative.

204

MESSAGE

UPS LDEV ! reports UPS "Low Output Voltage Shutdown" condition. (UPSERR 0204)

CAUSE

The specified UPS device reported a UPS "Low Output Voltage Shutdown" condition. This is a hardware malfunction within the UPS hardware or possibly in the equipment being powered from the UPS. The UPS has shut itself off.

ACTION

Call your Hewlett-Packard service representative.

512

MESSAGE

UPS Monitor UPS error: Lost communications with UPS LDEV !. That UPS is no longer being monitored. (UPSERR 0512)

CAUSE

The UPS Monitor had been monitoring the specified UPS LDEV successfully, then for some reason lost I/O communications with that UPS. The I/O interface cable or I/O interface hardware may have failed, or the UPS itself may have failed.

ACTION

Check the specified UPS's I/O interface cable and I/O interface connection at the computer. Check the UPS hardware for power connections and front panel indicators. If the cause is not found, call your HP service representative.

513

MESSAGE

UPS Monitor logic error: Attempted to map an invalid UPS power status condition. (UPSERR 0513)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

514

MESSAGE

UPS Monitor logic error: Attempted to map an invalid UPS alarm status condition. (UPSERR 0514)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

515

MESSAGE

UPS Monitor logic error: Attempted to map an invalid UPS status kind. (UPSERR 0515)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

516

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Receive_Msg. (UPSERR 0516)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

517

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Sendio. (UPSERR 0517)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

518

MESSAGE

UPS Monitor logic error: Invalid UID in UPS Table Entry when starting next UPS I/O request. (UPSERR 0518)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

519

MESSAGE

UPS Monitor logic error: Invalid UPS Number in UPS Table Entry when starting next UPS I/O request. (UPSERR 0519)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

520

MESSAGE

UPS Monitor logic error: Attempt to specify "no I/O request" when starting next UPS I/O request. (UPSERR 0520)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

521

MESSAGE

UPS Monitor logic error: Invalid Read request count when starting next UPS I/O request. (UPSERR 0521)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative

522

MESSAGE

UPS Monitor logic error: Invalid I/O function specified when starting next UPS I/O request. (UPSERR 0522)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

523

MESSAGE

UPS Monitor logic error: Attempt to start next UPS I/O request when previous UPS I/O request still running. (UPSERR 0523)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

524

MESSAGE

UPS Monitor logic error: Attempt to start more UPS I/O requests than there are UPS devices being monitored. (UPSERR 0524)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

525

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Rel_IO_Resources. (UPSERR 0525)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

526

MESSAGE

UPS Monitor logic error: I/O reply message received, not expected in present UPS operating state. (UPSERR 0526)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

527

MESSAGE

UPS Monitor logic error: I/O reply message received, but UPS operating state is undefined/unknown. (UPSERR 0527)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

528

MESSAGE

UPS Monitor logic error: UPS operating substate invalid while processing a "Go Online" I/O completion. (UPSERR 0528)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

529

MESSAGE

UPS Monitor logic error: UPS operating substate invalid while processing a "Set Terminal Controls" I/O completion. (UPSERR 0529)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

530

MESSAGE

UPS Monitor logic error: UPS number invalid in UID of I/O Reply message. (UPSERR 0530)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

531

MESSAGE

UPS Monitor logic error: Underflow of a UPS's number of I/O requests outstanding when processing a UPS I/O completion. (UPSERR 0531)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

532

MESSAGE

UPS Monitor logic error: Underflow of global number of UPS I/O requests outstanding when processing a UPS I/O completion. (UPSERR 0532)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

533

MESSAGE

UPS LDEV ! I/O Operation warning: Warning status returned by I/O system at completion of a UPS I/O request. (UPSWRN 0533)

CAUSE

This is a software-detected warning condition that indicates something unusual occurred in an I/O request made to a UPS by the UPS Monitor.

ACTION

If this warning appears only rarely, then no action is needed. If it appears frequently, then call your Hewlett-Packard service representative.

534

MESSAGE

UPS LDEV ! I/O Operation error: Error status returned by I/O system at completion of a UPS I/O request. (UPSERR 0534)

CAUSE

This is a software-detected error condition that indicates an error in the I/O software subsystems that the UPS Monitor uses to communicate with UPS devices.

ACTION

If this error appears only rarely, then no action is needed. If it appears frequently, then call your Hewlett-Packard service representative.

535

MESSAGE

UPS LDEV ! I/O Operation error: A status of "aborted" was returned by I/O system as completion status of a UPS I/O request. (UPSERR 0535)

CAUSE

This is a software-detected error condition that indicates an error in the I/O software subsystems that the UPS Monitor uses to communicate with UPS devices.

ACTION

If this error appears only rarely, then no action is needed. If it appears frequently, then call your Hewlett-Packard service representative.

536

MESSAGE

UPS LDEV ! I/O Operation error: UPS device failed to complete a Read I/O request in allotted time. The Read request timed out. (UPSERR 0536)

CAUSE

This is a software-detected error condition that indicates an error in the I/O software subsystems that the UPS Monitor uses to communicate with UPS devices. It could indicate a disconnected I/O cable or a UPS hardware malfunction.

ACTION

Check for proper connection of the UPS I/O interface cable at both ends. See if the UPS is powered-on. If those checks do not reveal the source of the problem, then call your Hewlett-Packard service representative.

538

MESSAGE

UPS Monitor logic error: UPS operating substate invalid while processing a "Monitoring" I/O completion. (UPSERR 0538)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

539

MESSAGE

UPS Monitor logic error: A UPS I/O completion reply message was received when none was expected, or the message received was not the one that was expected. (UPSERR 0539)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

540

MESSAGE

UPS Monitor UPS initialization: UPS LDEV ! was initialized successfully and is now being monitored. (UPSWRN 0540)

CAUSE

During system startup, the specified UPS device was successfully initialized by the UPS Monitor.

ACTION

No action is needed. This is merely an expected confirmation that the UPS and UPS Monitor software are operating correctly.

541

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Send_Msg. (UPSERR 0541)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

542

MESSAGE

UPS Monitor logic error: A UPS I/O reply message was received unexpectedly. The operating state of the UPS Monitor is inappropriate for receiving an I/O completion reply message. (UPSERR 0542)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

543

MESSAGE

UPS Monitor logic error: Processing of a UPS I/O completion message resulted in an unknown/undefined "io_result" variable. (UPSERR 0543)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

544

MESSAGE

UPS Monitor logic error: An invalid message was received by the UPS Monitor at its message port. The message is not recognized as any of the UPS Monitor's message types. (UPSERR 0544)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

545

MESSAGE

UPS Monitor logic error: An event message of invalid type was received by the UPS Monitor. The message is recognized as an event message, but the kind of event is unknown. (UPSERR 0545)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

546

MESSAGE

: UPS Monitor logic error: A timer message of invalid type was received by the UPS Monitor. The message is recognized as a timer message, but the kind of timer is unknown. (UPSERR 0546)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

547

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Get_Timer. (UPSERR 0547)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

548

MESSAGE

UPS Monitor logic error: UPS Monitor attempted to process a timer event message of an invalid type. (UPSERR 0548)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

549

MESSAGE

UPS Monitor logic error: During shutdown processing, while aborting UPS I/O requests, the UPS Monitor detected an "invalid number of UPS's configured" condition in its global table. (UPSERR 0549)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

550

MESSAGE

UPS Monitor logic error: During shutdown processing, while aborting UPS I/O requests, the UPS Monitor detected an "invalid number of UPS's monitored" condition in its global table. (UPSERR 0550)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

551

MESSAGE

UPS Monitor logic error: During shutdown processing, while aborting UPS I/O requests, the UPS Monitor detected a Nil UPS Table Pointer condition in its global table. (UPSERR 0551)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

552

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Abortio_Request. (UPSERR 0552)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

553

MESSAGE

UPS Monitor logic error: During shutdown processing, while aborting UPS I/O requests, the UPS Monitor detected an invalid UPS Table Entry. (UPSERR 0553)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

554

MESSAGE

UPS Monitor logic error: During shutdown processing, while aborting UPS I/O requests, the UPS Monitor detected an invalid count of UPS I/O requests outstanding. (UPSERR 0554)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

555

MESSAGE

UPS Monitor logic error: During shutdown processing, the UPS Monitor found that the UPS Monitor operating state was invalid when the shutdown event message was received. (UPSERR 0555)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

556

MESSAGE

UPS Monitor logic error: During shutdown processing, the UPS Monitor found that a shutdown operation was already in progress. (UPSERR 0556)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

557

MESSAGE

UPS Monitor logic error: During shutdown processing, when attempting to start the shutdown limit timer, the UPS Monitor found that a shutdown limit timer was already running. (UPSERR 0557)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

558

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Release_Timer. (UPSERR 0558)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

559

MESSAGE

UPS Monitor logic error: During UPS I/O completion processing in the "Set Terminal Controls" sequence, an I/O reply message was received that was not of the expected (Terminal Control) type. (UPSERR 0559)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

560

MESSAGE

UPS Monitor logic error: While processing an I/O Write completion, an I/O reply message was received that was not of the expected (Write) type. (UPSERR 0560)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

561

MESSAGE

UPS Monitor logic error: While processing an I/O Read completion, an I/O reply message was received that was not of the expected (Read) type. (UPSERR 0561)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

562

MESSAGE

UPS LDEV ! I/O Operation error: The actual Write data transfer length in a UPS Write I/O operation was not the expected (requested) transfer length. (UPSERR 0562)

CAUSE

This is a software-detected error condition that indicates an error in the I/O software subsystems that the UPS Monitor uses to communicate with UPS devices.

ACTION

Call your Hewlett-Packard service representative.

563

MESSAGE

UPS LDEV ! I/O Operation error: The actual Read data transfer length in a UPS Read I/O operation was too short, less than the minimum required Read transfer length. (UPSERR 0563)

CAUSE

This is a software-detected error condition that indicates an error in the I/O software subsystems that the UPS Monitor uses to communicate with UPS devices. It could also indicate an I/O interface hardware error, or a UPS hardware error

ACTION

Call your Hewlett-Packard service representative.

564

MESSAGE

UPS LDEV ! I/O Operation error: The actual Read data transfer length in a UPS Read I/O operation was too long, greater than the maxmimum requested Read transfer length. (UPSERR 0564)

CAUSE

This is a software-detected error condition that indicates an error in the I/O software subsystems that the UPS Monitor uses to communicate with UPS devices. It could also indicate an I/O interface error or a UPS hardware error.

ACTION

Call your Hewlett-Packard service representative.

565

MESSAGE

UPS Monitor logic error: UPS Monitor found global timer_id of zero, which is invalid, when it attempted to release the shutdown limit timer. (UPSERR 0565)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

566

MESSAGE

UPS Monitor logic error: UPS Monitor detected invalid parameters in a call to one of its procedures that inspects UPS Read data for matching to expected UPS input data patterns. (UPSERR 0566)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

567

MESSAGE

UPS LDEV ! I/O operation error: Data supplied by the UPS device in response to a Read I/O request did not match any of the allowable data patterns for that request. The Read will be re-done. (UPSERR 0567)

CAUSE

Possibly a poor I/O interface cable connection between the system and the UPS. Possibly electrical noise interference induced in the I/O interface cable or hardware. It could also indicate a malfunction of the UPS hardware.

ACTION

If this error appears only rarely, then no action is needed. If it appears frequently, then call your Hewlett-Packard service representative.

568

MESSAGE

UPS Monitor logic error: Table lookup of what should have been a valid UPS power status character failed to find the character in the lookup table. (UPSERR 0568)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

569

MESSAGE

UPS Monitor logic error: Table lookup of what should have been a valid UPS alarm status character failed to find the character in the lookup table. (UPSERR 0569)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

570

MESSAGE

UPS Monitor logic error: Table lookup of a UPS status character produced inconsistent results: The lookup procedure declared that it had found the character, but reported its type as "unknown". (UPSERR 570)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

571

MESSAGE

UPS Monitor logic error: After deciding that a UPS status character was valid, the UPS Monitor then failed to find that status character in its status lookup table. (UPSERR 0571)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

572

MESSAGE

UPS LDEV ! I/O operation error: The I/O completion status reported for the UPS I/O operation had an incorrect, unexpected I/O subsystem number in it. (UPSERR 0572)

CAUSE

This is a software-detected error condition that indicates an error in the I/O software subsystems that the UPS Monitor uses to communicate with UPS devices.

ACTION

Call your Hewlett-Packard service representative.

573

MESSAGE

UPS LDEV ! initialization error: After trying several times, the UPS Monitor has been unable to complete the initialization sequence of I/O operations for this UPS device. (UPSERR 0573)

CAUSE

Something is preventing the HP3000 system from communicating with the UPS. Possibly a bad I/O interface cable or bad I/O interface hardware at the system or at the UPS. Possibly a UPS hardware malfunction.

ACTION

Check the I/O interface cable for correct attachment, and check that the UPS is powered-on. Check that the system I/O configuration is correct. If the prob- lem is not found, then call your Hewlett-Packard service representative.

574

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Simple_Create_Process. (UPSERR 0574)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

575

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Find_Plabel_Info. (UPSERR 0575)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative

576

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure HPgetsysplabel. (UPSERR 0576)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

577

MESSAGE

UPS Monitor warning: Too many UPS devices have been configured in the system I/O configuration files. The UPS Monitor can not monitor all of them; it will monitor as many as it can. (UPSWRN 0577)

CAUSE

Incorrect system I/O configuration. The system I/O configuration, generated by SYSGEN and NMMGR configurators, contains more than 128 UPS devices, which is the maximum number that the UPS monitor can handle simultaneously.

ACTION

Review and correct the system I/O configuration, reducing the number of UPS devices specified in the configuration to an acceptable number.

578

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Start_Shut_NM. (UPSERR 0578)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

579

MESSAGE

UPS Monitor logic error: UPS Monitor attempted to create a "zero size" UPS Table. (UPSERR 0579)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

580

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure HPFOPEN. (UPSERR 0580)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

581

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure FCLOSE. (UPSERR 0581)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

582

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Release_Object. (UPSERR 0582)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

583

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Create_Object. (UPSERR 0583)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

584

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Create_Port. (UPSERR 0584)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

585

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Purge_Port. (UPSERR 0585)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

586

MESSAGE

UPS Monitor error: UPS Monitor was unable to create its UPS Table object. The UPS Monitor process can not operate without it, and isaborting itself. (UPSERR 0586)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

587

MESSAGE

UPS Monitor UPS error: Unable to start monitoring on UPS Ldev ! due to File System error in finding or opening the device. (UPSWRN 0587)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

588

MESSAGE

UPS Monitor logic error: UPS Monitor has detected that it has declared a UPS device to be "down", but the status that tells the reason for the "down" is invalid/undefined. (UPSERR 0588)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

589

MESSAGE

UPS LDEV ! initialization error: UPS Monitor was unable to allocate (open) this UPS device. This UPS device will not be monitored. (UPSERR 0589)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

590

MESSAGE

UPS Monitor error: UPS Monitor process initialization failed due to error in obtaining resources (data object, message port, etc.). (UPSERR 0590)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

591

MESSAGE

UPS Monitor warning: UPS Monitor finds no UPS devices configured in the system I/O configuration files. UPS Monitor is terminating itself. (UPSWRN 0591)

CAUSE

No UPSs have been configured in the system's I/O configuration files. This is an error if this system is supposed to have UPSs on it. This is not an error if this system is not supposed to have UPS devices on it.

ACTION

If this system is supposed to have UPS devices on it, then review and correct the system I/O configuration, and then restart the system. If this system is not supposed to have UPS devices on it, then no action is needed.

592

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Get_Ups_Devices_Count. (UPSERR 0592)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

593

MESSAGE

UPS LDEV ! initialization error: UPS Monitor was unable to locate this UPS LDEV via the File System's "Device Files" facility. (UPSERR 0593)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

594

MESSAGE

UPS Monitor logic error: Attempted to do status character mapping (table lookup) of an unknown/undefined UPS status character. (UPSERR 0594

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

595

MESSAGE

UPS Monitor information: UPS Monitor process has been launched by PROGEN and is starting-up its operation. (UPSWRN 0595)

CAUSE

The system has just been started-up, and the UPS Monitor software subsystem has automatically been started as well.

ACTION

No action is needed. This is merely an informational message confirming that the UPS Monitor software has been started.

596

MESSAGE

UPS Monitor information: UPS Monitor process has initialized itself successfully, and is ready to start UPS monitoring operations. (UPSWRN 0596)

CAUSE

After the UPS Monitor process was first started, it successfully initialized itself: it acquired the basic resources it needed to commence operations.

ACTION

No action is needed. This is merely an informational message that confirms that the UPS Monitor completed its process initialization successfully.

597

MESSAGE

UPS Monitor information: UPS Monitor process is shutting down, due to a normal system shutdown. (UPSWRN 0597)

CAUSE

The system operator initiated a normal Control-A Shutdown of the MPE/iX system. The UPS Monitor is shutting itself down as part of the overall system shutdown.

ACTION

No action is needed. This is merely an informational message that confirms that the UPS Monitor is shutting down due to a normal system shutdown.

598

MESSAGE

UPS Monitor system call error: Error status ! (Subsystem # !, Error # !) received from procedure Get_Ups_Devices_List. (UPSERR 0598)

CAUSE

This is a software-detected error condition that indicates an error occurred in a call to the specified MPE/iX Operating System procedure when that procedure was called by the UPS Monitor software.

ACTION

Call your Hewlett-Packard service representative.

599

MESSAGE

UPS Monitor warning: UPS Monitor process is shutting down and restarting itself due to an internal error condition. (UPSWRN 0599)

CAUSE

The UPS Monitor detected an error condition internal to its software, and is attempting to recover by restarting itself from the beginning of its process.

ACTION

If this warning appears only rarely, then no action is needed. If it appears frequently, then call your Hewlett-Packard service representative.

600

MESSAGE

UPS Monitor error: UPS Monitor process is shutting down, due to an unrecoverable internal error condition. (UPSERR 0600)

CAUSE

The UPS Monitor software detected an error condition within its processing from which it can not recover. Accordingly, it is shutting itself down, ending the UPS monitoring processing.

ACTION

This should rarely, if ever, happen in practice. You can re-boot the system to see if the UPS Monitor will run successfully after a new startup of the system. If the problem persists, call your Hewlett-Packard service representative.

601

MESSAGE

UPS Monitor logic error: UPS Monitor process unable to obtain list of UPS LDEVS from HLIO after successfully obtaining number of UPS devices from HLIO. (UPSERR 0601)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.

602

MESSAGE

UPS Monitor information: UPS Monitor process startup of UPS devices failed, due to inability to get UPS devices' allocation information from the system. (UPSERR 0602)

CAUSE

This is a software-detected error condition that indicates an error in the UPS Monitor software or in some other system software, or a system memory error.

ACTION

Call your Hewlett-Packard service representative.