UPS LDEV ! reports loss of AC input power.
(UPSERR 0033)
CAUSE
The specified UPS device reported that it detected
an input power failure. There has been an AC power failure somewhere
in the power path leading into the UPS. The UPS has switched to
its internal battery pack to supply reserve power.
ACTION
If the power failure is brief, not long enough to
exhaust the UPS battery, no action is needed. Otherwise, determine what
is causing the power loss and take action to restore the power before
the UPS battery becomes exhausted.
35
MESSAGE
UPS LDEV ! reports AC input power "Bypass Mode".
(UPSWRN 0035)
CAUSE
The specified UPS device has been placed into its
"AC Power Bypass Mode" of operation. This should only occur when
an HP Customer Engineer is servicing the UPS and intends to put
the UPS into "Bypass Mode".
ACTION
No action is needed if this message occurs during Customer
Engineer servicing of the UPS.If this message occurs during normal
system operation, there is probably a hardware problem in the UPS.
Call your HP service representative.
36
MESSAGE
UPS LDEV ! reports AC input power restored.
(UPSWRN 0036)
CAUSE
The specified UPS device had lost its AC input power
in the past, and now the AC input power has been restored. If the
UPS is operating correctly, it will now switch from battery operation
back to normal AC power operation.
ACTION
No action is needed. The system automatically returns
to normal operation when all UPS devices (there may be one or several
UPS devices on a system) detect that normal AC input power is present
following a power loss at any UPS.
The specified UPS had lost its AC input power some
time ago and has been supplying reserve power from its battery. AC
input power has not been restored yet, causing the battery to be
drained down to a "low charge" power level.
ACTION
Locate and correct the cause of the AC power failure.
If AC power is not restored within the next two minutes, the UPS
battery will be exhausted and the UPS output AC power will fail,
causing power loss to the computer equipment.
41
MESSAGE
UPS LDEV ! reports AC output power turned off.
(UPSERR 0041)
CAUSE
The specified UPS device has turned off its AC output power.
Someone may have mistakenly turned off the UPS' power switch, or
the UPS may have malfunctioned. Whatever equipment was receiving
power from the UPS has now lost power.
ACTION
Investigate and correct the problem at the UPS.
Turn on all power control switches on the UPS. If the computer (CPU)
lost power, you will have to re-boot the system after restoring
the UPS power.
Some time ago, the specified UPS device had reported
a UPS "System Failure" condition. Now, the "System Failure" condition
within the UPS device has been corrected and the UPS is reporting
that it has returned to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a UPS "Inverter Failure" condition. Now, the "Inverter Failure"
condition within the UPS device has been corrected and the UPS is
reporting a return to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a "Battery Not Present" condition. Now, the "Battery Not Present"
condition within the UPS has been corrected and the UPS is reporting
that it has returned to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a UPS "Charger Fault" condition. Now, the "Charger Fault" condition
within the UPS device has been corrected and the UPS is reporting
that it has returned to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported an "Overload
Shutdown" condition. Now, the "Overload Shutdown" condition
within the UPS device has been corrected and the UPS is reporting
a return to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a "UPS High Ambient Temp- erature Shutdown" condition. Now, the
"High-Ambient Temperature Shutdown" con- dition has been corrected.
The UPS is reporting a return to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a UPS "Overload" condition. Now, the UPS "Overload" condition has
been corrected and the UPS is reporting that it has returned to
normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a UPS "High Ambient Temp- erature" condition. Now, the "High Ambient
Temperature" condition has been corrected and the UPS is reporting
that it has returned to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a UPS "Battery Test Fail" condition. Now, the "Battery Test Fail"
condition within the UPS device has been corrected and the UPS is
reporting a return to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a UPS "High Battery Volt- age" condition. Now, the "High Battery
Voltage" condition in the UPS device has been corrected and the
UPS is reporting a return to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported a UPS "Low
Battery Volt- age" condition. Now, the "Low Battery Voltage" condition
in the UPS device has been corrected and the UPS is reporting
a return to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a UPS "High Output Volt- age Shutdown" condition. Now, the "High
Output Voltage Shutdown" condition has been cleared and the UPS
is reporting a return to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
Some time ago, the specified UPS device had reported
a UPS "Low Output Voltage Shutdown" condition. Now, the "Low Output
Voltage Shutdown" condition has been corrected and the UPS is reporting
a return to normal operation.
ACTION
No action is needed. This message merely confirms
that a previously reported problem has been corrected.
The specified UPS device reported a "UPS Inverter Fail" condition.
This is a hardware malfunction condition within the UPS. The DC-to-AC
power inverter within the UPS has malfunctioned.
The specified UPS device reported a "Battery Not Present" condition.
This is a hardware malfunction condition within the UPS.
The UPS hardware logic perceives that the UPS battery pack
is not connected.
The specified UPS device reported a UPS "Charger Fault" condition.
This is a hardware malfunction condition within the UPS. The UPS'
internal battery charger circuitry has malfunctioned.
The specified UPS device reported a UPS "Overload Shutdown"
condition. Too much power was being drawn from the UPS AC output by
the computer equipment being powered from this UPS. That equipment
may be malfunctioning.
The specified UPS device reported a UPS "High Ambient Temperature
Shutdown" condition. The temperature of the UPS hardware became
too high to permit safe operation, and the UPS turned itself off
to prevent equipment damage.
ACTION
If the computer room has become too warm, take steps
to cool the room. If room temperature is not the problem, there
has probably been a hardware malfunction. Call your Hewlett-Packard
service representative.
The specified UPS device reported a UPS "Overload" condition.
The equipment being powered by the UPS is drawing too much power
from the UPS AC output. If the excessive power draw continues, the
UPS may reach an "Overload Shutdown".
The specified UPS device reported a UPS "High Ambient Temperature"
condition. The UPS has detected an abnormally high temperature in
the UPS hardware. If the temperature rises further, the UPS may
reach "High Temperature Shutdown".
ACTION
If the computer room has become too warm, take steps
to cool the room. If room temperature is not the problem, there
has probably been a hardware malfunction. Call your Hewlett-Packard
service representative.
The specified UPS device reported a UPS "Battery
Test Fail" condition. This is a hardware malfunction within the UPS
hardware. The UPS logic perceives that the UPS battery is not working
properly.
The specified UPS device reported a UPS "High Battery Voltage"
condition. This is a hardware malfunction within the UPS hardware.
The UPS logic perceives that the UPS battery is not working
properly.
The specified UPS device reported a UPS "Low Battery Voltage"
condition. This is a hardware malfunction within the UPS hardware.
The UPS logic perceives that the UPS battery is not working
properly.
The specified UPS device reported a UPS "High Output Voltage
Shutdown" condi-tion. This is a hardware malfunction within the
UPS hardware or possibly in the equipment being powered from the
UPS. The UPS has shut itself off.
The specified UPS device reported a UPS "Low Output Voltage
Shutdown" condition. This is a hardware malfunction within the UPS
hardware or possibly in the equipment being powered from the UPS.
The UPS has shut itself off.
ACTION
Call your Hewlett-Packard service representative.
512
MESSAGE
UPS Monitor UPS error: Lost communications with UPS LDEV !. That
UPS is no longer being monitored. (UPSERR 0512)
CAUSE
The UPS Monitor had been monitoring the specified
UPS LDEV successfully, then for some reason lost I/O communications
with that UPS. The I/O interface cable or I/O interface hardware
may have failed, or the UPS itself may have failed.
ACTION
Check the specified UPS's I/O interface cable and
I/O interface connection at the computer. Check the UPS hardware
for power connections and front panel indicators. If the cause is
not found, call your HP service representative.
513
MESSAGE
UPS Monitor logic error: Attempted to map an invalid UPS power
status condition. (UPSERR 0513)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
514
MESSAGE
UPS Monitor logic error: Attempted to map an invalid UPS alarm
status condition. (UPSERR 0514)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
515
MESSAGE
UPS Monitor logic error: Attempted to map an invalid UPS
status kind. (UPSERR 0515)
CAUSE
This is a software-detected error condition that indicates an
error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
516
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Receive_Msg.
(UPSERR 0516)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
517
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Sendio. (UPSERR 0517)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
518
MESSAGE
UPS Monitor logic error: Invalid UID in UPS Table Entry when
starting next UPS I/O request. (UPSERR 0518)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
519
MESSAGE
UPS Monitor logic error: Invalid UPS Number in UPS Table Entry
when starting next UPS I/O request. (UPSERR 0519)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
520
MESSAGE
UPS Monitor logic error: Attempt to specify "no I/O request"
when starting next UPS I/O request. (UPSERR 0520)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
521
MESSAGE
UPS Monitor logic error: Invalid Read request count when
starting next UPS I/O request. (UPSERR 0521)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative
522
MESSAGE
UPS Monitor logic error: Invalid I/O function specified when
starting next UPS I/O request. (UPSERR 0522)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
523
MESSAGE
UPS Monitor logic error: Attempt to start next UPS I/Orequest
when previous UPS I/O request still running. (UPSERR 0523)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
524
MESSAGE
UPS Monitor logic error: Attempt to start more UPS I/O requests
than there are UPS devices being monitored. (UPSERR 0524)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
525
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Rel_IO_Resources.
(UPSERR 0525)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
527
MESSAGE
UPS Monitor logic error: I/O reply message received, but UPS
operating state is undefined/unknown. (UPSERR 0527)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
528
MESSAGE
UPS Monitor logic error: UPS operating substate invalid while
processing a "Go Online" I/O completion. (UPSERR 0528)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
529
MESSAGE
UPS Monitor logic error: UPS operating substate invalid while
processing a "Set Terminal Controls" I/O completion.
(UPSERR 0529)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
530
MESSAGE
UPS Monitor logic error: UPS number invalid in UID of I/O
Reply message. (UPSERR 0530)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
531
MESSAGE
UPS Monitor logic error: Underflow of a UPS's number of I/O
requests outstanding when processing a UPS I/O completion.
(UPSERR 0531)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
532
MESSAGE
UPS Monitor logic error: Underflow of global number of UPS I/O
requests outstanding when processing a UPS I/O completion.
(UPSERR 0532)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
533
MESSAGE
UPS LDEV ! I/O Operation warning: Warning status returned by
I/O system at completion of a UPS I/O request.
(UPSWRN 0533)
CAUSE
This is a software-detected warning condition that indicates
something unusual occurred in an I/O request made to a UPS by the
UPS Monitor.
ACTION
If this warning appears only rarely, then no action
is needed. If it appears frequently, then call your Hewlett-Packard
service representative.
534
MESSAGE
UPS LDEV ! I/O Operation error: Error status returned by I/O
system at completion of a UPS I/O request. (UPSERR 0534)
CAUSE
This is a software-detected error condition that
indicates an error in the I/O software subsystems that the UPS Monitor
uses to communicate with UPS devices.
ACTION
If this error appears only rarely, then no action is needed. If it
appears frequently, then call your Hewlett-Packard service
representative.
535
MESSAGE
UPS LDEV ! I/O Operation error: A status of "aborted" was
returned by I/O system as completion status of a UPS I/O request.
(UPSERR 0535)
CAUSE
This is a software-detected error condition that indicates
an error in the I/O software subsystems that the UPS Monitor
uses to communicate with UPS devices.
ACTION
If this error appears only rarely, then no action is needed. If it
appears frequently, then call your Hewlett-Packard service
representative.
536
MESSAGE
UPS LDEV ! I/O Operation error: UPS device failed to complete a
Read I/O request in allotted time. The Read request timed out.
(UPSERR 0536)
CAUSE
This is a software-detected error condition that
indicates an error in the I/O software subsystems that the UPS Monitor
uses to communicate with UPS devices. It could indicate a disconnected
I/O cable or a UPS hardware malfunction.
ACTION
Check for proper connection of the UPS I/O interface
cable at both ends. See if the UPS is powered-on. If those checks do
not reveal the source of the problem, then call your Hewlett-Packard
service representative.
538
MESSAGE
UPS Monitor logic error: UPS operating substate invalid while
processing a "Monitoring" I/O completion. (UPSERR 0538)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
539
MESSAGE
UPS Monitor logic error: A UPS I/O completion reply message was
received when none was expected, or the message received was not the
one that was expected. (UPSERR 0539)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
540
MESSAGE
UPS Monitor UPS initialization: UPS LDEV ! was initialized
successfully and is now being monitored. (UPSWRN 0540)
CAUSE
During system startup, the specified UPS device
was successfully initialized by the UPS Monitor.
ACTION
No action is needed. This is merely an expected confirmation
that the UPS and UPS Monitor software are operating correctly.
541
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Send_Msg. (UPSERR 0541)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
542
MESSAGE
UPS Monitor logic error: A UPS I/O reply message was received
unexpectedly. The operating state of the UPS Monitor is inappropriate
for receiving an I/O completion reply message.
(UPSERR 0542)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
543
MESSAGE
UPS Monitor logic error: Processing of a UPS I/O completion
message resulted in an unknown/undefined "io_result" variable.
(UPSERR 0543)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
544
MESSAGE
UPS Monitor logic error: An invalid message was received by the
UPS Monitor at its message port. The message is not recognized as any
of the UPS Monitor's message types. (UPSERR 0544)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
545
MESSAGE
UPS Monitor logic error: An event message of invalid type was
received by the UPS Monitor. The message is recognized as an event
message, but the kind of event is unknown. (UPSERR 0545)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
546
MESSAGE
: UPS Monitor logic error: A timer message of invalid type was
received by the UPS Monitor. The message is recognized as a timer
message, but the kind of timer is unknown. (UPSERR 0546)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
547
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Get_Timer.
(UPSERR 0547)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
548
MESSAGE
UPS Monitor logic error: UPS Monitor attempted to process a
timer event message of an invalid type. (UPSERR 0548)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
549
MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected an "invalid number
of UPS's configured" condition in its global table.
(UPSERR 0549)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
Errors 550 - 699
550
MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected an "invalid number
of UPS's monitored" condition in its global table.
(UPSERR 0550)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
551
MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected a Nil UPS Table
Pointer condition in its global table. (UPSERR 0551)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
552
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Abortio_Request.
(UPSERR 0552)
CAUSE
This is a software-detected error condition that indicates an
error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
553
MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected an invalid UPS
Table Entry. (UPSERR 0553)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
554
MESSAGE
UPS Monitor logic error: During shutdown processing, while
aborting UPS I/O requests, the UPS Monitor detected an invalid count
of UPS I/O requests outstanding. (UPSERR 0554)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
555
MESSAGE
UPS Monitor logic error: During shutdown processing, the UPS
Monitor found that the UPS Monitor operating state was invalid when
the shutdown event message was received. (UPSERR 0555)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
556
MESSAGE
UPS Monitor logic error: During shutdown processing, the UPS
Monitor found that a shutdown operation was already in progress.
(UPSERR 0556)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
557
MESSAGE
UPS Monitor logic error: During shutdown processing, when
attempting to start the shutdown limit timer, the UPS Monitor found
that a shutdown limit timer was already running.
(UPSERR 0557)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
558
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Release_Timer.
(UPSERR 0558)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
559
MESSAGE
UPS Monitor logic error: During UPS I/O completion processing in
the "Set Terminal Controls" sequence, an I/O reply message was received
that was not of the expected (Terminal Control) type.
(UPSERR 0559)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
560
MESSAGE
UPS Monitor logic error: While processing an I/O Write
completion, an I/O reply message was received that was not of the
expected (Write) type. (UPSERR 0560)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
561
MESSAGE
UPS Monitor logic error: While processing an I/O Read
completion, an I/O reply message was received that was not of the
expected (Read) type. (UPSERR 0561)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
562
MESSAGE
UPS LDEV ! I/O Operation error: The actual Write data transfer
length in a UPS Write I/O operation was not the expected (requested)
transfer length. (UPSERR 0562)
CAUSE
This is a software-detected error condition that
indicates an error in the I/O software subsystems that the UPS Monitor
uses to communicate with UPS devices.
ACTION
Call your Hewlett-Packard service representative.
563
MESSAGE
UPS LDEV ! I/O Operation error: The actual Read data transfer
length in a UPS Read I/O operation was too short, less than the minimum
required Read transfer length. (UPSERR 0563)
CAUSE
This is a software-detected error condition that
indicates an error in the I/O software subsystems that the UPS Monitor
uses to communicate with UPS devices. It could also indicate an
I/O interface hardware error, or a UPS hardware error
ACTION
Call your Hewlett-Packard service representative.
564
MESSAGE
UPS LDEV ! I/O Operation error: The actual Read data transfer
length in a UPS Read I/O operation was too long, greater than the
maxmimum requested Read transfer length. (UPSERR 0564)
CAUSE
This is a software-detected error condition that
indicates an error in the I/O software subsystems that the UPS Monitor
uses to communicate with UPS devices. It could also indicate an
I/O interface error or a UPS hardware error.
ACTION
Call your Hewlett-Packard service representative.
565
MESSAGE
UPS Monitor logic error: UPS Monitor found global timer_id of
zero, which is invalid, when it attempted to release the shutdown
limit timer. (UPSERR 0565)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
566
MESSAGE
UPS Monitor logic error: UPS Monitor detected invalid parameters
in a call to one of its procedures that inspects UPS Read data for
matching to expected UPS input data patterns.
(UPSERR 0566)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
567
MESSAGE
UPS LDEV ! I/O operation error: Data supplied by the UPS device
in response to a Read I/O request did not match any of the allowable
data patterns for that request. The Read will be re-done.
(UPSERR 0567)
CAUSE
Possibly a poor I/O interface cable connection between
the system and the UPS. Possibly electrical noise interference induced
in the I/O interface cable or hardware. It could also indicate a
malfunction of the UPS hardware.
ACTION
If this error appears only rarely, then no action is needed. If it
appears frequently, then call your Hewlett-Packard service
representative.
568
MESSAGE
UPS Monitor logic error: Table lookup of what should have been
a valid UPS power status character failed to find the character in the
lookup table. (UPSERR 0568)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
569
MESSAGE
UPS Monitor logic error: Table lookup of what should have been
a valid UPS alarm status character failed to find the character in the
lookup table. (UPSERR 0569)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
570
MESSAGE
UPS Monitor logic error: Table lookup of a UPS status character
produced inconsistent results: The lookup procedure declared that it
had found the character, but reported its type as "unknown".
(UPSERR 570)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
571
MESSAGE
UPS Monitor logic error: After deciding that a UPS status
character was valid, the UPS Monitor then failed to find that status
character in its status lookup table. (UPSERR 0571)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
572
MESSAGE
UPS LDEV ! I/O operation error: The I/O completion status
reported for the UPS I/O operation had an incorrect, unexpected I/O
subsystem number in it. (UPSERR 0572)
CAUSE
This is a software-detected error condition that
indicates an error in the I/O software subsystems that the UPS Monitor
uses to communicate with UPS devices.
ACTION
Call your Hewlett-Packard service representative.
573
MESSAGE
UPS LDEV ! initialization error: After trying several times,
the UPS Monitor has been unable to complete the initialization sequence
of I/O operations for this UPS device. (UPSERR 0573)
CAUSE
Something is preventing the HP3000 system from communicating with
the UPS. Possibly a bad I/O interface cable or bad I/O interface
hardware at the system or at the UPS. Possibly a UPS hardware
malfunction.
ACTION
Check the I/O interface cable for correct attachment,
and check that the UPS is powered-on. Check that the system I/O
configuration is correct. If the prob- lem is not found, then call
your Hewlett-Packard service representative.
574
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Simple_Create_Process.
(UPSERR 0574)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
575
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Find_Plabel_Info.
(UPSERR 0575)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative
576
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure HPgetsysplabel.
(UPSERR 0576)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
577
MESSAGE
UPS Monitor warning: Too many UPS devices have been configured
in the system I/O configuration files. The UPS Monitor can not monitor
all of them; it will monitor as many as it can.
(UPSWRN 0577)
CAUSE
Incorrect system I/O configuration. The system I/O configuration,
generated by SYSGEN and NMMGR configurators, contains more than
128 UPS devices, which is the maximum number that the UPS monitor
can handle simultaneously.
ACTION
Review and correct the system I/O configuration,
reducing the number of UPS devices specified in the configuration to
an acceptable number.
578
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Start_Shut_NM.
(UPSERR 0578)
CAUSE
This is a software-detected error condition that indicates an error
occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
579
MESSAGE
UPS Monitor logic error: UPS Monitor attempted to create a
"zero size" UPS Table. (UPSERR 0579)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
580
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure HPFOPEN. (UPSERR 0580)
CAUSE
This is a software-detected error condition that
indicates an error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
581
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure FCLOSE. (UPSERR 0581)
CAUSE
This is a software-detected error condition that
indicates an error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
582
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Release_Object.
(UPSERR 0582)
CAUSE
This is a software-detected error condition that
indicates an error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
583
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Create_Object.
(UPSERR 0583)
CAUSE
This is a software-detected error condition that
indicates an error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
584
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Create_Port.
(UPSERR 0584)
CAUSE
This is a software-detected error condition that
indicates an error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
585
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Purge_Port.
(UPSERR 0585)
CAUSE
This is a software-detected error condition that
indicates an error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
586
MESSAGE
UPS Monitor error: UPS Monitor was unable to create its UPS
Table object. The UPS Monitor process can not operate without it, and
isaborting itself. (UPSERR 0586)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
587
MESSAGE
UPS Monitor UPS error: Unable to start monitoring on UPS Ldev !
due to File System error in finding or opening the device.
(UPSWRN 0587)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
588
MESSAGE
UPS Monitor logic error: UPS Monitor has detected that it has
declared a UPS device to be "down", but the status that tells the
reason for the "down" is invalid/undefined. (UPSERR 0588)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
589
MESSAGE
UPS LDEV ! initialization error: UPS Monitor was unable to
allocate (open) this UPS device. This UPS device will not be monitored.
(UPSERR 0589)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
590
MESSAGE
UPS Monitor error: UPS Monitor process initialization failed
due to error in obtaining resources (data object, message port, etc.).
(UPSERR 0590)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
591
MESSAGE
UPS Monitor warning: UPS Monitor finds no UPS devices configured
in the system I/O configuration files. UPS Monitor is terminating
itself. (UPSWRN 0591)
CAUSE
No UPSs have been configured in the system's I/O configuration
files. This is an error if this system is supposed to have UPSs
on it. This is not an error if this system is not supposed to have
UPS devices on it.
ACTION
If this system is supposed to have UPS devices on it, then review
and correct the system I/O configuration, and then restart
the system. If this system is not supposed to have UPS devices on
it, then no action is needed.
592
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Get_Ups_Devices_Count.
(UPSERR 0592)
CAUSE
This is a software-detected error condition that
indicates an error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
593
MESSAGE
UPS LDEV ! initialization error: UPS Monitor was unable to
locate this UPS LDEV via the File System's "Device Files" facility.
(UPSERR 0593)
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
594
MESSAGE
UPS Monitor logic error: Attempted to do status character
mapping (table lookup) of an unknown/undefined UPS status character.
(UPSERR 0594
CAUSE
This is a software-detected error condition that
indicates an error in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
595
MESSAGE
UPS Monitor information: UPS Monitor process has been launched
by PROGEN and is starting-up its operation. (UPSWRN 0595)
CAUSE
The system has just been started-up, and the UPS Monitor software
subsystem has automatically been started as well.
ACTION
No action is needed. This is merely an informational message
confirming that the UPS Monitor software has been started.
596
MESSAGE
UPS Monitor information: UPS Monitor process has initialized
itself successfully, and is ready to start UPS monitoring operations.
(UPSWRN 0596)
CAUSE
After the UPS Monitor process was first started, it successfully
initialized itself: it acquired the basic resources
it needed to commence operations.
ACTION
No action is needed. This is merely an informational message
that confirms that the UPS Monitor completed its process initialization
successfully.
597
MESSAGE
UPS Monitor information: UPS Monitor process is shutting down,
due to a normal system shutdown. (UPSWRN 0597)
CAUSE
The system operator initiated a normal Control-A Shutdown
of the MPE/iX system. The UPS Monitor is shutting itself down as
part of the overall system shutdown.
ACTION
No action is needed. This is merely an informational message
that confirms that the UPS Monitor is shutting down due to a normal
system shutdown.
598
MESSAGE
UPS Monitor system call error: Error status ! (Subsystem # !,
Error # !) received from procedure Get_Ups_Devices_List.
(UPSERR 0598)
CAUSE
This is a software-detected error condition that
indicates an error occurred in a call to the specified MPE/iX Operating
System procedure when that procedure was called by the UPS Monitor
software.
ACTION
Call your Hewlett-Packard service representative.
599
MESSAGE
UPS Monitor warning: UPS Monitor process is shutting down and
restarting itself due to an internal error condition.
(UPSWRN 0599)
CAUSE
The UPS Monitor detected an error condition internal
to its software, and is attempting to recover by restarting itself
from the beginning of its process.
ACTION
If this warning appears only rarely, then no action
is needed. If it appears frequently, then call your Hewlett-Packard
service representative.
600
MESSAGE
UPS Monitor error: UPS Monitor process is shutting down, due to
an unrecoverable internal error condition. (UPSERR 0600)
CAUSE
The UPS Monitor software detected an error condition within
its processing from which it can not recover. Accordingly, it is
shutting itself down, ending the UPS monitoring processing.
ACTION
This should rarely, if ever, happen in practice. You can re-boot the
system to see if the UPS Monitor will run successfully
after a new startup of the system. If the problem persists, call
your Hewlett-Packard service representative.
601
MESSAGE
UPS Monitor logic error: UPS Monitor process unable to obtain
list of UPS LDEVS from HLIO after successfully obtaining number of UPS
devices from HLIO. (UPSERR 0601)
CAUSE
This is a software-detected error condition that indicates an error
in the UPS Monitor software or in some other system
software, or a system memory error.
ACTION
Call your Hewlett-Packard service representative.
602
MESSAGE
UPS Monitor information: UPS Monitor process startup of UPS
devices failed, due to inability to get UPS devices' allocation
information from the system. (UPSERR 0602)
CAUSE
This is a software-detected error condition that indicates an
error in the UPS Monitor software or in some other system
software, or a system memory error.